JEET, Vol. 13, No. 5, September 2018
Power Swing Detection Using rms Current Measurements
Farzad Razavi
Area A - Electric Power Engineering
Abstract During a power swing, distance relays may mistakenly spread fault throughout the power grid, causing a great deal of damage. In some cases, such mistakes can cause global outages. For this reason, it is critical to make a distinction between power swings and faults in distance relays. In this paper, a new method is proposed based on RMS measurement to differentiate between faults and power swings. The proposed method was tested on two standard grids, demonstrating its capability in detecting a power swing and simultaneous fault with power swing. This method required no specific configurations, and was independent of grid type and zoning type of distance relays. This feature in practice allows the relay to be installed on any grid with any kind of coordination. In protective relays, the calculations applied to the microprocessor is of great importance. Distance relays are constantly calculating the current RMS values for protection purposes. This mitigates the computations in the microprocessor to detect power swings. The proposed method was able to differentiate between a fault and a power swing. Furthermore, it managed to detect faults occurring simultaneously with power swings.
Keyword Power swing,Power system protection,Distance relay,RMS,Transient in power system.